home *** CD-ROM | disk | FTP | other *** search
/ HIV AIDS Resource Guide / HIV-AIDS Resource Guide.iso / STAT / FEDERAL / BUILD4.ASC < prev    next >
Text File  |  1994-01-14  |  52KB  |  1,205 lines

  1. /* Part 4 of 4 of accesibility requirements follow. */
  2.  
  3. A4.1.3 Accessible Buildings:  New Construction.
  4.  
  5. A4.1.3(5) Only full passenger elevators are covered by the 
  6. accessibility provisions of 4.10.  Materials and equipment 
  7. hoists, freight elevators not intended for passenger use, 
  8. dumbwaiters, and construction elevators are not covered by these 
  9. guidelines.  If a building is exempt from the elevator 
  10. requirement, it is not necessary to provide a platform lift or 
  11. other means of vertical access in lieu of an elevator.
  12.  
  13. Under Exception 4, platform lifts are allowed where existing 
  14. conditions make it impractical to install a ramp or elevator.  
  15. Such conditions generally occur where it is essential to provide 
  16. access to small raised or lowered areas where space may not be 
  17. available for a ramp.  Examples include, but are not limited to, 
  18. raised pharmacy platforms, commercial offices raised above a 
  19. sales floor, or radio and news booths.
  20.  
  21. A4.1.3(9) Supervised automatic sprinkler systems have built in 
  22. signals for monitoring features of the system such as the opening 
  23. and closing of water control valves, the power supplies for 
  24. needed pumps, water tank levels, and for indicating conditions 
  25. that will impair the satisfactory operation of the sprinkler 
  26. system.  Because of these monitoring features, supervised 
  27. automatic sprinkler systems have a high level of satisfactory 
  28. performance and response to fire conditions.
  29.  
  30. A4.1.3(10) If an odd number of drinking fountains is provided on 
  31. a floor, the requirement in 4.1.3(10)(b) may be met by rounding 
  32. down the odd number to an even number and calculating 50% of the 
  33. even number.  When more than one drinking fountain on a floor is 
  34. required to comply with 4.15, those fountains should be dispersed 
  35. to allow wheelchair users convenient access.  For example, in a 
  36. large facility such as a convention center that has water 
  37. fountains at several locations on a floor, the accessible water 
  38. fountains should be located so that wheelchair users do not have
  39. to travel a greater distance than other people to use a drinking 
  40. fountain.
  41.  
  42. A4.1.3(17)(b) In addition to the requirements of section 
  43. 4.1.3(17)(b), the installation of additional volume controls is 
  44. encouraged.  Volume controls may be installed on any telephone.
  45.  
  46. A4.1.3(19)(a) Readily removable or folding seating units may be 
  47. installed in lieu of providing an open space for wheelchair 
  48. users.  Folding seating units are usually two fixed seats that 
  49. can be easily folded into a fixed center bar to allow for one or 
  50. two open spaces for wheelchair users when necessary.  These units 
  51. are more easily adapted than removable seats which generally 
  52. require the seat to be removed in advance by the facility 
  53. management.
  54.  
  55. Either a sign or a marker placed on seating with removable or 
  56.                            
  57. folding arm rests is required by this section.  Consideration 
  58. should be given for ensuring identification of such seats in a 
  59. darkened theater.  For example, a marker which contrasts (light 
  60. on dark or dark on light) and which also reflects light could be 
  61. placed on the side of such seating so as to be visible in a 
  62. lighted auditorium and also to reflect light from a flashlight.
  63.  
  64. A4.1.6 Accessible Buildings: Alterations.
  65.  
  66. A4.1.6(1)(h) When an entrance is being altered, it is preferable 
  67. that those entrances being altered be made accessible to the 
  68. extent feasible.
  69.  
  70. A4.2 Space Allowances and Reach Ranges.
  71.  
  72. A4.2.1 Wheelchair Passage Width.
  73.  
  74.     (1)    Space Requirements for Wheelchairs.  Many persons who 
  75. use wheelchairs need a 30 in (760 mm) clear opening width for 
  76. doorways, gates, and the like, when the latter are entered 
  77. head-on.  If the person is unfamiliar with a building, if 
  78. competing traffic is heavy, if sudden or frequent movements are 
  79. needed, or if the wheelchair must be turned at an opening, then 
  80. greater clear widths are needed.  For most situations, the 
  81. addition of an inch of leeway on either side is sufficient.  
  82. Thus, a minimum clear width of 32 in (815 mm) will provide 
  83. adequate clearance.  However, when an opening or a restriction in 
  84. a passageway is more than 24 in (610 mm) long, it is essentially 
  85. a passageway and must be at least 36 in (915 mm) wide.
  86.  
  87.     (2)    Space Requirements for Use of Walking Aids.  Although 
  88. people who use walking aids can maneuver through clear width 
  89. openings of 32 in (815 mm), they need 36 in (915 mm) wide 
  90. passageways and walks for comfortable gaits.  Crutch tips, often 
  91. extending down at a wide angle, are a hazard in narrow 
  92. passageways where they might not be seen by other pedestrians.  
  93. Thus, the 36 in (915 mm) width provides a safety allowance both 
  94. for the person with a disability and for others.
  95.  
  96.     (3)    Space Requirements for Passing.  Able-bodied persons 
  97. in winter clothing, walking straight ahead with arms swinging, 
  98. need 32 in (815 mm) of width, which includes 2 in (50 mm) on 
  99. either side for sway, and another 1 in (25 mm) tolerance on 
  100. either side for clearing nearby objects or other pedestrians.  
  101. Almost all wheelchair users and those who use walking aids can 
  102. also manage within this 32 in (815 mm) width for short distances.  
  103. Thus, two streams of traffic can pass in 64 in (1625 mm) in a 
  104. comfortable flow.  Sixty inches (1525 mm) provides a minimum 
  105. width for a somewhat more restricted flow.  If the clear width is 
  106. less than 60 in (1525 mm), two wheelchair users will not be able 
  107. to pass but will have to seek a wider place for passing.  
  108. Forty-eight inches (1220 mm) is the minimum width needed for an 
  109. ambulatory person to pass a nonambulatory or semi-ambulatory 
  110. person.  Within this 48 in (1220 mm) width, the ambulatory person 
  111. will have to twist to pass a wheelchair user, a person with a 
  112. service animal, or a semi-ambulatory person.  There will be 
  113. little leeway for swaying or missteps (see Fig. A1).
  114.  
  115. A4.2.3 Wheelchair Turning Space.  These guidelines specify a 
  116. minimum space of 60 in (1525 mm) diameter or a 60 in by 60 in 
  117. (1525 mm by 1525 mm) T-shaped space for a pivoting 180-degree 
  118. turn of a wheelchair.  This space is usually satisfactory for 
  119. turning around, but many people will not be able to turn without 
  120. repeated tries and bumping into surrounding objects.  The space 
  121. shown in Fig. A2 will allow most wheelchair users to complete 
  122. U-turns without difficulty.
  123.  
  124. A4.2.4 Clear Floor or Ground Space for Wheelchairs.  The 
  125. wheelchair and user shown in Fig. A3 represent typical dimensions 
  126. for a large adult male.  The space requirements in this guideline 
  127. are based upon maneuvering clearances that will accommodate most 
  128. wheelchairs.  Fig. A3 provides a uniform reference for design not 
  129. covered by this guideline.
  130.  
  131. A4.2.5 & A4.2.6 Reach.  Reach ranges for persons seated in 
  132. wheelchairs may be further clarified by Fig. A3(a).  These 
  133. drawings approximate in the plan view the information shown in 
  134. Fig. 4, 5, and 6.
  135.  
  136. A4.3 Accessible Route.
  137.  
  138. A4.3.1 General.
  139.  
  140.     (1)    Travel Distances.  Many people with mobility 
  141. impairments can move at only very slow speeds; for many, 
  142. traveling 200 ft (61
  143. m)    could take about 2 minutes.  This assumes a rate of about 1.5 
  144. ft/s (455 mm/s) on level ground.  It also assumes that the 
  145. traveler would move continuously.  However, on trips over 100 ft 
  146. (30 m), disabled people are apt to rest frequently, which 
  147. substantially increases their trip times.  Resting periods of 2 
  148. minutes for every 100 ft (30 m) can be used to estimate travel 
  149. times for people with severely limited stamina.  In inclement 
  150. weather, slow progress and resting can greatly increase a 
  151. disabled person's exposure to the elements.
  152.  
  153.     (2)    Sites.  Level, indirect routes or those with running 
  154. slopes lower than 1:20 can sometimes provide more convenience 
  155. than direct routes with maximum allowable slopes or with ramps.
  156.  
  157. A4.3.10 Egress.  Because people with disabilities may visit, be 
  158. employed or be a resident in any building, emergency management 
  159. plans with specific provisions to ensure their safe evacuation 
  160. also play an essential role in fire safety and life safety.
  161.  
  162. A4.3.11.3 Stairway Width.  A 48 in (1220 mm) wide exit stairway 
  163. is needed to allow assisted evacuation (e.g., carrying a person 
  164. in a wheelchair) without encroaching on the exit path for 
  165. ambulatory persons.
  166.  
  167. A4.3.11.4 Two-way Communication.  It is essential that emergency 
  168. communication not be dependent on voice communications alone 
  169. because the safety of people with hearing or speech impairments 
  170. could be jeopardized.  The visible signal requirement could be 
  171. satisfied with something as simple as a button in the area of 
  172. rescue assistance that lights, indicating that help is on the 
  173. way, when the message is answered at the point of entry.
  174.  
  175. A4.4 Protruding Objects.
  176.  
  177. A4.4.1 General.  Service animals are trained to recognize and 
  178. avoid hazards.  However, most people with severe impairments of 
  179. vision use the long cane as an aid to mobility.  The two 
  180. principal cane techniques are the touch technique, where the cane 
  181. arcs from side to side and touches points outside both shoulders; 
  182. and the diagonal technique, where the cane is held in a 
  183. stationary position diagonally across the body with the cane tip 
  184. touching or just above the ground at a point outside one shoulder 
  185. and the handle or grip extending to a point outside the other 
  186. shoulder.  The touch technique is used primarily in uncontrolled 
  187. areas, while the diagonal technique is used primarily in certain 
  188. limited, controlled, and familiar environments.  Cane users are 
  189. often trained to use both techniques.
  190.  
  191. Potential hazardous objects are noticed only if they fall within 
  192. the detection range of canes (see Fig.  A4).  Visually impaired 
  193. people walking toward an object can detect an overhang if its 
  194. lowest surface is not higher than 27 in (685 mm).  When walking 
  195. alongside protruding objects, they cannot detect overhangs.  
  196. Since proper cane and service animal techniques keep people away 
  197. from the edge of a path or from walls, a slight overhang of no 
  198. more than 4 in (100 mm) is not hazardous.
  199.  
  200. A4.5 Ground and Floor Surfaces.
  201.  
  202. A4.5.1 General.  People who have difficulty walking or 
  203. maintaining balance or who use crutches, canes, or walkers, and 
  204. those with restricted gaits are particularly sensitive to 
  205. slipping and tripping hazards.  For such people, a stable and 
  206. regular surface is necessary for safe walking, particularly on 
  207. stairs.  Wheelchairs can be propelled most easily on surfaces 
  208. that are hard, stable, and regular.  Soft loose surfaces such as 
  209. shag carpet, loose sand or gravel, wet clay, and irregular 
  210. surfaces such as cobblestones can significantly impede wheelchair 
  211. movement.
  212.  
  213. Slip resistance is based on the frictional force necessary to 
  214. keep a shoe heel or crutch tip from slipping on a walking surface 
  215. under conditions likely to be found on the surface.  While the 
  216. dynamic coefficient of friction during walking varies in a 
  217. complex and non-uniform way, the static coefficient of friction, 
  218. which can be measured in several ways, provides a close 
  219. approximation of the slip resistance of a surface.  Contrary to 
  220. popular belief, some slippage is necessary to walking, especially 
  221. for persons with restricted gaits; a truly "non-slip" surface 
  222. could not be negotiated.
  223.  
  224. The Occupational Safety and Health Administration recommends that 
  225. walking surfaces have a static coefficient of friction of 0.5.  A 
  226. research project sponsored by the Architectural and 
  227. Transportation Barriers Compliance Board (Access Board) conducted 
  228. tests with persons with disabilities and concluded that a higher 
  229. coefficient of friction was needed by such persons.  A static 
  230. coefficient of friction of 0.6 is recommended for accessible 
  231. routes and 0.8 for ramps.
  232.  
  233. It is recognized that the coefficient of friction varies 
  234. considerably due to the presence of contaminants, water, floor 
  235. finishes, and other factors not under the control of the designer 
  236. or builder and not subject to design and construction guidelines 
  237. and that compliance would be difficult to measure on the building 
  238. site.  Nevertheless, many common building materials suitable for 
  239. flooring are now labeled with information on the static 
  240. coefficient of friction.  While it may not be possible to compare 
  241. one product directly with another, or to guarantee a constant 
  242. measure, builders and designers are encouraged to specify 
  243. materials with appropriate values.  As more products include 
  244. information on slip resistance, improved uniformity in 
  245. measurement and specification is likely.  The Access Board's 
  246. advisory guidelines on Slip Resistant Surfaces provides 
  247. additional information on this subject.
  248.  
  249. Cross slopes on walks and ground or floor surfaces can cause 
  250. considerable difficulty in propelling a wheelchair in a straight 
  251. line.
  252.  
  253. A4.5.3 Carpet.  Much more needs to be done in developing both 
  254. quantitative and qualitative criteria for carpeting (i.e., 
  255. problems associated with texture and weave need to be studied).  
  256. However, certain functional characteristics are well established.  
  257. When both carpet and padding are used, it is desirable to have 
  258. minimum movement (preferably none) between the floor and the pad 
  259. and the pad and the carpet which would allow the carpet to hump 
  260. or warp.  In heavily trafficked areas, a thick, soft (plush) pad 
  261. or cushion, particularly in combination with long carpet pile, 
  262. makes it difficult for individuals in wheelchairs and those with 
  263. other ambulatory disabilities to get about.  Firm carpeting can 
  264. be achieved through proper selection and combination of pad and 
  265. carpet, sometimes with the elimination of the pad or cushion, and 
  266. with proper installation.  Carpeting designed with a weave that 
  267. causes a zig-zag effect when wheeled across is strongly 
  268. discouraged.
  269.  
  270. A4.6 Parking and Passenger Loading Zones.
  271.  
  272. A4.6.3 Parking Spaces.  The increasing use of vans with side- 
  273. mounted lifts or ramps by persons with disabilities has 
  274. necessitated some revisions in specifications for parking spaces 
  275. and adjacent access aisles. The typical accessible parking space 
  276. is 96 in (2440 mm) wide with an adjacent 60 in (1525 mm) access 
  277. aisle. However, this aisle does not permit lifts or ramps to be 
  278. deployed and still leave room for a person using a wheelchair or 
  279. other mobility aid to exit the lift platform or ramp. In tests 
  280. conducted with actual lift/van/wheelchair combinations, (under a 
  281. Board-sponsored Accessible Parking and Loading Zones Project) 
  282. researchers found that a space and aisle totaling almost 204 in 
  283. (5180 mm) wide was needed to deploy a lift and exit conveniently.  
  284. The "van accessible" parking space required by these guidelines 
  285. provides a 96 in (2440 mm) wide space with a 96 in (2440 mm) 
  286. adjacent access aisle which is just wide enough to maneuver and 
  287. exit from a side mounted lift.  If a 96 in (2440 mm) access aisle 
  288. is placed between two spaces, two "van accessible" spaces are 
  289. created. Alternatively, if the wide access aisle is provided at 
  290. the end of a row (an area often unused), it may be possible to 
  291. provide the wide access aisle without additional space (see Fig.  
  292. A5(a)).
  293.  
  294. A sign is needed to alert van users to the presence of the wider 
  295. aisle, but the space is not intended to be restricted only to 
  296. vans.
  297.  
  298. "Universal" Parking Space Design.  An alternative to the 
  299. provision of a percentage of spaces with a wide aisle, and the 
  300. associated need to include additional signage, is the use of what 
  301. has been called the "universal" parking space design.  Under this 
  302. design, all accessible spaces are 132 in (3350 mm) wide with a 60 
  303. in (1525 mm) access aisle (see Fig. A5(b)).  One advantage to 
  304. this design is that no additional signage is needed because all 
  305. spaces can accommodate a van with a side-mounted lift or ramp.  
  306. Also, there is no competition between cars and vans for spaces 
  307. since all spaces can accommodate either.  Furthermore, the wider 
  308. space permits vehicles to park to one side or the other within 
  309. the 132 in (3350 mm) space to allow persons to exit and enter the 
  310. vehicle on either the driver or passenger side, although, in some 
  311. cases, this would require exiting or entering without a marked 
  312. access aisle.
  313.  
  314. An essential consideration for any design is having the access 
  315. aisle level with the parking space. Since a person with a 
  316. disability, using a lift or ramp, must maneuver within the access 
  317. aisle, the aisle cannot include a ramp or sloped area. The access 
  318. aisle must be connected to an accessible route to the appropriate 
  319. accessible entrance of a building or facility. The parking access 
  320. aisle must either blend with the accessible route or have a curb 
  321. ramp complying with 4.7. Such a curb ramp opening must be located 
  322. within the access aisle boundaries, not within the parking space 
  323. boundaries. Unfortunately, many facilities are designed with a 
  324. ramp that is blocked when any vehicle parks in the accessible 
  325. space. Also, the required dimensions of the access aisle cannot 
  326. be restricted by planters, curbs or wheel stops.
  327.  
  328. A4.6.4 Signage.  Signs designating parking places for disabled 
  329. people can be seen from a driver's seat if the signs are mounted 
  330. high enough above the ground and located at the front of a 
  331. parking space.
  332.  
  333. A4.6.5 Vertical Clearance.  High-top vans, which disabled people 
  334. or transportation services often use, require higher clearances 
  335. in parking garages than automobiles.
  336.  
  337. A4.8 Ramps.
  338.  
  339. A4.8.1 General.  Ramps are essential for wheelchair users if 
  340. elevators or lifts are not available to connect different levels.  
  341. However, some people who use walking aids have difficulty with 
  342. ramps and prefer stairs.
  343.  
  344. A4.8.2 Slope and Rise.  Ramp slopes between 1:16 and 1:20 are 
  345. preferred.  The ability to manage an incline is related to both 
  346. its slope and its length.  Wheelchair users with disabilities 
  347. affecting their arms or with low stamina have serious difficulty 
  348. using inclines.  Most ambulatory people and most people who use 
  349. wheelchairs can manage a slope of 1:16.  Many people cannot 
  350. manage a slope of 1:12 for 30 ft (9 m).
  351.  
  352. A4.8.4 Landings.  Level landings are essential toward maintaining 
  353. an aggregate slope that complies with these guidelines.  A ramp 
  354. landing that is not level causes individuals using wheelchairs to 
  355. tip backward or bottom out when the ramp is approached.
  356.  
  357. A4.8.5 Handrails.  The requirements for stair and ramp handrails 
  358. in this guideline are for adults.  When children are principal 
  359. users in a building or facility, a second set of handrails at an 
  360. appropriate height can assist them and aid in preventing 
  361. accidents.
  362.  
  363. A4.9 Stairs.
  364.  
  365. A4.9.1 Minimum Number.  Only interior and exterior stairs 
  366. connecting levels that are not connected by an elevator, ramp, or 
  367. other accessible means of vertical access have to comply with 
  368. 4.9.
  369.  
  370. A4.10 Elevators.
  371.  
  372. A4.10.6 Door Protective and Reopening Device.  The required door 
  373. reopening device would hold the door open for 20 seconds if the 
  374. doorway remains obstructed.  After 20 seconds, the door may begin 
  375. to close.  However, if designed in accordance with ASME 
  376. A17.1-1990, the door closing movement could still be stopped if a 
  377. person or object exerts sufficient force at any point on the door 
  378. edge.
  379.  
  380. A4.10.7 Door and Signal Timing for Hall Calls.  This paragraph 
  381. allows variation in the location of call buttons, advance time 
  382. for warning signals, and the door-holding period used to meet the 
  383. time requirement.
  384.  
  385. A4.10.12 Car Controls.  Industry-wide standardization of elevator 
  386. control panel design would make all elevators significantly more 
  387. convenient for use by people with severe visual impairments.  In 
  388. many cases, it will be possible to locate the highest control on 
  389. elevator panels within 48 in (1220 mm) from the floor.
  390.  
  391. A4.10.13 Car Position Indicators.  A special button may be 
  392. provided that would activate the audible signal within the given 
  393. elevator only for the desired trip, rather than maintaining the 
  394. audible signal in constant operation.
  395.  
  396. A4.10.14 Emergency Communications.  A device that requires no 
  397. handset is easier to use by people who have difficulty reaching.  
  398. Also, small handles on handset compartment doors are not usable 
  399. by people who have difficulty grasping.
  400.  
  401. Ideally, emergency two-way communication systems should provide 
  402. both voice and visual display intercommunication so that persons 
  403. with hearing impairments and persons with vision impairments can 
  404. receive information regarding the status of a rescue.  A voice 
  405. intercommunication system cannot be the only means of 
  406. communication because it is not accessible to people with speech 
  407. and hearing impairments.  While a voice intercommunication system 
  408. is not required, at a minimum, the system should provide both an 
  409. audio and visual indication that a rescue is on the way.
  410.  
  411. A4.11 Platform Lifts (Wheelchair Lifts).
  412.  
  413. A4.11.2 Other Requirements.  Inclined stairway chairlifts, and 
  414. inclined and vertical platform lifts (wheelchair lifts) are 
  415. available for short-distance, vertical transportation of people 
  416. with disabilities.  Care should be taken in selecting lifts as 
  417. some lifts are not equally suitable for use by both wheelchair 
  418. users and semi-ambulatory individuals.
  419.  
  420. A4.12 Windows.
  421.  
  422. A4.12.1 General.  Windows intended to be operated by occupants in 
  423. accessible spaces should comply with 4.12.
  424.  
  425. A4.12.2 Window Hardware.  Windows requiring pushing, pulling, or 
  426. lifting to open (for example, double-hung, sliding, or casement 
  427. and awning units without cranks) should require no more than 5 
  428. lbf (22.2 N) to open or close.  Locks, cranks, and other window 
  429. hardware should comply with 4.27.
  430.  
  431. A4.13 Doors.
  432.  
  433. A4.13.8 Thresholds at Doorways.  Thresholds and surface height 
  434. changes in doorways are particularly inconvenient for wheelchair 
  435. users who also have low stamina or restrictions in arm movement 
  436. because complex maneuvering is required to get over the level 
  437. change while operating the door.
  438.  
  439. A4.13.9 Door Hardware.  Some disabled persons must push against a 
  440. door with their chair or walker to open it.  Applied kickplates 
  441. on doors with closers can reduce required maintenance by 
  442. withstanding abuse from wheelchairs and canes.  To be effective, 
  443. they should cover the door width, less approximately 2 in (51 
  444. mm), up to a height of 16 in (405 mm) from its bottom edge and be 
  445. centered across the width of the door.
  446.  
  447. A4.13.10 Door Closers.  Closers with delayed action features give 
  448. a person more time to maneuver through doorways.  They are 
  449. particularly useful on frequently used interior doors such as 
  450. entrances to toilet rooms.
  451.  
  452. A4.13.11 Door Opening Force.  Although most people with 
  453. disabilities can exert at least 5 lbf (22.2N), both pushing and 
  454. pulling from a stationary position, a few people with severe 
  455. disabilities cannot exert 3 lbf (13.13N).  Although some people 
  456. cannot manage the allowable forces in this guideline and many 
  457. others have difficulty, door closers must have certain minimum 
  458. closing forces to close doors satisfactorily.  Forces for pushing 
  459. or pulling doors open are measured with a push-pull scale under 
  460. the following conditions:
  461.  
  462.     (1)    Hinged doors:  Force applied perpendicular to the door 
  463. at the door opener or 30 in (760 mm) from the hinged side, 
  464. whichever is farther from the hinge.
  465.  
  466.     (2)    Sliding or folding doors:  Force applied parallel to 
  467. the door at the door pull or latch.
  468.  
  469.     (3)    Application of force:  Apply force gradually so that 
  470. the applied force does not exceed the resistance of the door.  In 
  471. high-rise buildings, air-pressure differentials may require a 
  472. modification of this specification in order to meet the 
  473. functional intent.
  474.  
  475. A4.13.12 Automatic Doors and Power-Assisted Doors.  Sliding 
  476. automatic doors do not need guard rails and are more convenient 
  477. for wheelchair users and visually impaired people to use.  If 
  478. slowly opening automatic doors can be reactivated before their 
  479. closing cycle is completed, they will be more convenient in busy 
  480. doorways.
  481.  
  482. A4.15 Drinking Fountains and Water Coolers.
  483.  
  484. A4.15.2 Spout Height.  Two drinking fountains, mounted side by 
  485. side or on a single post, are usable by people with disabilities 
  486. and people who find it difficult to bend over.
  487.  
  488. A4.16 Water Closets.
  489.  
  490. A4.16.3 Height.  Height preferences for toilet seats vary 
  491. considerably among disabled people.  Higher seat heights may be 
  492. an advantage to some ambulatory disabled people, but are often a 
  493. disadvantage for wheelchair users and others.  Toilet seats 18 in 
  494. (455 mm) high seem to be a reasonable compromise.  Thick seats 
  495. and filler rings are available to adapt standard fixtures to 
  496. these requirements.
  497.  
  498. A4.16.4 Grab Bars.  Fig. A6(a) and (b) show the diagonal and side 
  499. approaches most commonly used to transfer from a wheelchair to a 
  500. water closet.  Some wheelchair users can transfer from the front 
  501. of the toilet while others use a 90-degree approach.  Most people 
  502. who use the two additional approaches can also use either the 
  503. diagonal approach or the side approach.
  504.  
  505. A4.16.5 Flush Controls.  Flush valves and related plumbing can be 
  506. located behind walls or to the side of the toilet, or a toilet 
  507. seat lid can be provided if plumbing fittings are directly behind 
  508. the toilet seat.  Such designs reduce the chance of injury and 
  509. imbalance caused by leaning back against the fittings.  Flush 
  510. controls for tank-type toilets have a standardized mounting 
  511. location on the left side of the tank (facing the tank).  Tanks 
  512. can be obtained by special order with controls mounted on the 
  513. right side.  If administrative authorities require flush controls 
  514. for flush valves to be located in a position that conflicts with 
  515. the location of the rear grab bar, then that bar may be split or 
  516. shifted toward the wide side of the toilet area.
  517.  
  518. A4.17 Toilet Stalls.
  519.  
  520. A4.17.3 Size and Arrangement.  This section requires use of the 
  521. 60 in (1525 mm) standard stall (Figure 30(a)) and permits the 36 
  522. in (915 mm) or 48 in (1220 mm) wide alternate stall (Figure 
  523. 30(b)) only in alterations where provision of the standard stall 
  524. is technically infeasible or where local plumbing codes prohibit 
  525. reduction in the number of fixtures.  A standard stall provides a 
  526. clear space on one side of the water closet to enable persons who 
  527. use wheelchairs to perform a side or diagonal transfer from the 
  528. wheelchair to the water closet.  However, some persons with 
  529. disabilities who use mobility aids such as walkers, canes or 
  530. crutches are better able to use the two parallel grab bars in the 
  531. 36 in (915 mm) wide alternate stall to achieve a standing 
  532. position.
  533.  
  534. In large toilet rooms, where six or more toilet stalls are 
  535. provided, it is therefore required that a 36 in (915 mm) wide 
  536. stall with parallel grab bars be provided in addition to the 
  537. standard stall required in new construction.  The 36 in (915 mm) 
  538. width is necessary to achieve proper use of the grab bars; wider 
  539. stalls would position the grab bars too far apart to be easily 
  540. used and narrower stalls would position the grab bars too close 
  541. to the water closet.  Since the stall is primarily intended for 
  542. use by persons using canes, crutches and walkers, rather than 
  543. wheelchairs, the length of the stall could be conventional.  The 
  544. door, however, must swing outward to ensure a usable space for 
  545. people who use crutches or walkers.
  546.  
  547. A4.17.5 Doors.  To make it easier for wheelchair users to close 
  548. toilet stall doors, doors can be provided with closers, spring 
  549. hinges, or a pull bar mounted on the inside surface of the door 
  550. near the hinge side.
  551.  
  552. A4.19 Lavatories and Mirrors.
  553.  
  554. A4.19.6 Mirrors.  If mirrors are to be used by both ambulatory 
  555. people and wheelchair users, then they must be at least 74 in 
  556. (1880 mm) high at their topmost edge.  A single full length 
  557. mirror can accommodate all people, including children.
  558.  
  559. A4.21 Shower Stalls.
  560.  
  561. A4.21.1 General.  Shower stalls that are 36 in by 36 in (915 mm 
  562. by 915 mm) wide provide additional safety to people who have 
  563. difficulty maintaining balance because all grab bars and walls 
  564. are within easy reach.  Seated people use the walls of 36 in by 
  565. 36 in (915 mm by 915 mm) showers for back support.  Shower stalls 
  566. that are 60 in (1525 mm) wide and have no curb may increase 
  567. usability of a bathroom by wheelchair users because the shower 
  568. area provides additional maneuvering space.
  569.  
  570. A4.22 Toilet Rooms.
  571.  
  572. A4.22.3    Clear Floor Space.  In many small facilities, single- user 
  573. restrooms may be the only facilities provided for all building 
  574. users.  In addition, the guidelines allow the use of "unisex" or 
  575. "family" accessible toilet rooms in alterations when technical 
  576. infeasibility can be demonstrated.  Experience has shown that the 
  577. provision of accessible "unisex" or single-user restrooms is a 
  578. reasonable way to provide access for wheelchair users and any 
  579. attendants, especially when attendants are of the opposite sex.  
  580. Since these facilities have proven so useful, it is often 
  581. considered advantageous to install a "unisex" toilet room in new 
  582. facilities in addition to making the multi-stall restrooms 
  583. accessible, especially in shopping malls, large auditoriums, and 
  584. convention centers.
  585.  
  586. Figure 28 (section 4.16) provides minimum clear floor space 
  587. dimensions for toilets in accessible "unisex" toilet rooms.  The 
  588. dotted lines designate the minimum clear floor space, depending 
  589. on the direction of approach, required for wheelchair users to 
  590. transfer onto the water closet.  The dimensions of 48 in (1220 
  591. mm) and 60 in (1525 mm), respectively, correspond to the space 
  592. required for the two common transfer approaches utilized by 
  593. wheelchair users (see Fig. A6).  It is important to keep in mind 
  594. that the placement of the lavatory to the immediate side of the 
  595. water closet will preclude the side approach transfer illustrated 
  596. in Figure A6(b).  To accommodate the side transfer, the space 
  597. adjacent to the water closet must remain clear of obstruction for 
  598. 42 in (1065 mm) from the centerline of the toilet (Figure 28) and 
  599. the lavatory must not be located within this clear space.  A 
  600. turning circle or T-turn, the clear floor space at the lavatory, 
  601. and maneuvering space at the door must be considered when 
  602. determining the possible wall locations.  A privacy latch or 
  603. other accessible means of ensuring privacy during use should be 
  604. provided at the door.
  605.  
  606. RECOMMENDATIONS:
  607.  
  608. 1.    In new construction, accessible single-user restrooms may be 
  609. desirable in some situations because they can accommodate a wide 
  610. variety of building users.  However, they cannot be used in lieu 
  611. of making the multi-stall toilet rooms accessible as required.
  612.  
  613. 2.    Where strict compliance to the guidelines for accessible toilet 
  614. facilities is technically infeasible in the alteration of 
  615. existing facilities, accessible "unisex" toilets are a reasonable 
  616. alternative.
  617.  
  618. 3.    In designing accessible single-user restrooms, the provisions 
  619. of adequate space to allow a side transfer will provide 
  620. accommodation to the largest number of wheelchair users.
  621.  
  622. A4.23 Bathrooms, Bathing Facilities, and Shower Rooms.
  623.  
  624. A4.23.3 Clear Floor Space.  Figure A7 shows two possible 
  625. configurations of a toilet room with a roll-in shower.  The 
  626. specific shower shown is designed to fit exactly within the 
  627. dimensions of a standard bathtub.  Since the shower does not have 
  628. a lip, the floor space can be used for required maneuvering 
  629. space.  This would permit a toilet room to be smaller than would 
  630. be permitted with a bathtub and still provide enough floor space 
  631. to be considered accessible.  This design can provide 
  632. accessibility in facilities where space is at a premium (i.e., 
  633. hotels and medical care facilities).  The alternate roll-in 
  634. shower (Fig. 57b) also provides sufficient room for the "T-turn" 
  635. and does not require plumbing to be on more than one wall.
  636.  
  637. A4.23.9 Medicine Cabinets.  Other alternatives for storing 
  638. medical and personal care items are very useful to disabled 
  639. people.  Shelves, drawers, and floor-mounted cabinets can be 
  640. provided within the reach ranges of disabled people.
  641.  
  642. A4.26 Handrails, Grab Bars, and Tub and Shower Seats.
  643.  
  644. A4.26.1 General.  Many disabled people rely heavily upon grab 
  645. bars and handrails to maintain balance and prevent serious falls.  
  646. Many people brace their forearms between supports and walls to 
  647. give them more leverage and stability in maintaining balance or 
  648. for lifting.  The grab bar clearance of 1-1/2 in (38 mm) required 
  649. in this guideline is a safety clearance to prevent injuries 
  650. resulting from arms slipping through the openings.  It also 
  651. provides adequate gripping room.
  652.  
  653. A4.26.2 Size and Spacing of Grab Bars and Handrails.  This 
  654. specification allows for alternate shapes of handrails as long as 
  655. they allow an opposing grip similar to that provided by a 
  656. circular section of 1-1/4 in to 1-1/2 in (32 mm to 38 mm).
  657.  
  658. A4.27 Controls and Operating Mechanisms.
  659.  
  660. A4.27.3 Height.  Fig. A8 further illustrates mandatory and 
  661. advisory control mounting height provisions for typical 
  662. equipment.
  663.  
  664. Electrical receptacles installed to serve individual appliances 
  665. and not intended for regular or frequent use by building 
  666. occupants are not required to be mounted within the specified 
  667. reach ranges.  Examples would be receptacles installed 
  668. specifically for wall-mounted clocks, refrigerators, and 
  669. microwave ovens.
  670.  
  671. A4.28 Alarms.
  672.  
  673. A4.28.2 Audible Alarms.  Audible emergency signals must have an 
  674. intensity and frequency that can attract the attention of 
  675. individuals who have partial hearing loss.  People over 60 years 
  676. of age generally have difficulty perceiving frequencies higher 
  677. than 10,000 Hz.  An alarm signal which has a periodic element to 
  678. its signal, such as single stroke bells (clang-pause-clang- 
  679. pause), hi-low (up-down-up-down) and fast whoop (on-off-on-off) 
  680. are best.  Avoid continuous or reverberating tones.  Select a 
  681. signal which has a sound characterized by three or four clear 
  682. tones without a great deal of "noise" in between.
  683.  
  684. A4.28.3 Visual Alarms.  The specifications in this section do not 
  685. preclude the use of zoned or coded alarm systems.
  686.  
  687. A4.28.4 Auxiliary Alarms.  Locating visual emergency alarms in 
  688. rooms where persons who are deaf may work or reside alone can 
  689. ensure that they will always be warned when an emergency alarm is 
  690. activated.  To be effective, such devices must be located and 
  691. oriented so that they will spread signals and reflections 
  692. throughout a space or raise the overall light level sharply.  
  693. However, visual alarms alone are not necessarily the best means 
  694. to alert sleepers.  A study conducted by Underwriters Laboratory 
  695. (UL) concluded that a flashing light more than seven times 
  696. brighter was required (110 candela v. 15 candela, at the same 
  697. distance) to awaken sleepers as was needed to alert awake 
  698. subjects in a normal daytime illuminated room.
  699.  
  700. For hotel and other rooms where people are likely to be asleep, a 
  701. signal-activated vibrator placed between mattress and box spring 
  702. or under a pillow was found by UL to be much more effective in 
  703. alerting sleepers.  Many readily available devices are sound- 
  704. activated so that they could respond to an alarm clock, clock 
  705. radio, wake-up telephone call or room smoke detector.  Activation 
  706. by a building alarm system can either be accomplished by a 
  707. separate circuit activating an auditory alarm which would, in 
  708. turn, trigger the vibrator or by a signal transmitted through the 
  709. ordinary 110-volt outlet.  Transmission of signals through the 
  710. power line is relatively simple and is the basis of common, 
  711. inexpensive remote light control systems sold in many department 
  712. and electronic stores for home use.  So-called "wireless" 
  713. intercoms operate on the same principal.
  714.  
  715. A4.29 Detectable Warnings.
  716.  
  717. A4.29.2 Detectable Warnings on Walking Surfaces.  The material 
  718. used to provide contrast should contrast by at least 70%.  
  719. Contrast in percent is determined by:
  720.  
  721. Contrast = [(B1 - B2)/B1] x 100
  722.  
  723. where B1 = light reflectance value (LRV) of the lighter area and 
  724. B2 = light reflectance value (LRV) of the darker area.
  725.  
  726. Note that in any application both white and black are never 
  727. absolute; thus, B1 never equals 100 and B2 is always greater than 
  728. 0.
  729.  
  730. A4.30 Signage.
  731.  
  732. A4.30.1 General.  In building complexes where finding locations 
  733. independently on a routine basis may be a necessity (for example, 
  734. college campuses), tactile maps or prerecorded instructions can 
  735. be very helpful to visually impaired people.  Several maps and 
  736. auditory instructions have been developed and tested for specific 
  737. applications.  The type of map or instructions used must be based 
  738. on the information to be communicated, which depends highly on 
  739. the type of buildings or users.
  740.  
  741. Landmarks that can easily be distinguished by visually impaired 
  742. individuals are useful as orientation cues.  Such cues include 
  743. changes in illumination level, bright colors, unique patterns, 
  744. wall murals, location of special equipment or other architectural 
  745. features.
  746.  
  747. Many people with disabilities have limitations in movement of 
  748. their heads and reduced peripheral vision.  Thus, signage 
  749. positioned perpendicular to the path of travel is easiest for 
  750. them to notice.  People can generally distinguish signage within 
  751. an angle of 30 degrees to either side of the centerlines of their 
  752. faces without moving their heads.
  753.  
  754. A4.30.2 Character Proportion.  The legibility of printed 
  755. characters is a function of the viewing distance, character 
  756. height, the ratio of the stroke width to the height of the 
  757. character, the contrast of color between character and 
  758. background, and print font.  The size of characters must be based 
  759. upon the intended viewing distance.  A severely nearsighted 
  760. person may have to be much closer to recognize a character of a 
  761. given size than a person with normal visual acuity.
  762.  
  763. A4.30.4 Raised and Brailled Characters and Pictorial Symbol Signs 
  764. (Pictograms).  The standard dimensions for literary Braille are 
  765. as follows:
  766.  
  767.     Dot diameter    .059 in.
  768.  
  769.     Inter-dot spacing    .090 in.
  770.  
  771. Horizontal separation between cells .241 in.
  772.  
  773.     Vertical separation between cells    .395 in.
  774.  
  775. Raised borders around signs containing raised characters may make 
  776. them confusing to read unless the border is set far away from the 
  777. characters.  Accessible signage with descriptive materials about 
  778. public buildings, monuments, and objects of cultural interest may 
  779. not provide sufficiently detailed and meaningful information.  
  780. Interpretive guides, audio tape devices, or other methods may be 
  781. more effective in presenting such information.
  782.  
  783. A4.30.5 Finish and Contrast.  An eggshell finish (11 to 19 degree 
  784. gloss on 60 degree glossimeter) is recommended.  Research 
  785. indicates that signs are more legible for persons with low vision 
  786. when characters contrast with their background by at least 70 
  787. percent.  Contrast in percent shall be determined by:
  788.  
  789. Contrast = [(B1 - B2)/B1] x 100
  790.  
  791. where B1 = light reflectance value (LRV) of the lighter area and 
  792. B2 = light reflectance value (LRV) of the darker area.
  793.  
  794. Note that in any application both white and black are never 
  795. absolute; thus, B1 never equals 100 and B2 is always greater than 
  796. 0.
  797.  
  798. The greatest readability is usually achieved through the use of 
  799. light-colored characters or symbols on a dark background.
  800.  
  801. A4.30.7 Symbols of Accessibility for Different Types of Listening 
  802. Systems.  Paragraph 4 of this section requires signage indicating 
  803. the availability of an assistive listening system.  An 
  804. appropriate message should be displayed with the international 
  805. symbol of access for hearing loss since this symbol conveys 
  806. general accessibility for people with hearing loss.  Some 
  807. suggestions are:
  808.  
  809. INFRARED
  810. ASSISTIVE LISTENING SYSTEM
  811. AVAILABLE
  812. ----PLEASE ASK----
  813.  
  814. AUDIO LOOP IN USE
  815. TURN T-SWITCH FOR
  816. BETTER HEARING
  817. ----OR ASK FOR HELP----
  818.  
  819. FM
  820. ASSISTIVE LISTENING
  821. SYSTEM AVAILABLE
  822. ----PLEASE ASK----
  823.  
  824. The symbol may be used to notify persons of the availability of 
  825. other auxiliary aids and services such as: real time captioning, 
  826. captioned note taking, sign language interpreters, and oral 
  827. interpreters.
  828.  
  829. A4.30.8 Illumination Levels.  Illumination levels on the sign 
  830. surface shall be in the 100 to 300 lux range (10 to 30 
  831. footcandles) and shall be uniform over the sign surface.  Signs 
  832. shall be located such that the illumination level on the surface 
  833. of the sign is not significantly exceeded by the ambient light or 
  834. visible bright lighting source behind or in front of the sign.
  835.  
  836. A4.31 Telephones.
  837.  
  838. A4.31.3 Mounting Height.  In localities where the dial-tone first 
  839. system is in operation, calls can be placed at a coin telephone 
  840. through the operator without inserting coins.  The operator 
  841. button is located at a height of 46 in (1170 mm) if the coin slot 
  842. of the telephone is at 54 in (1370 mm).  A generally available 
  843. public telephone with a coin slot mounted lower on the equipment 
  844. would allow universal installation of telephones at a height of 
  845. 48 in (1220 mm) or less to all operable parts.
  846.  
  847. A4.31.9 Text Telephones.  A public text telephone may be an 
  848. integrated text telephone pay phone unit or a conventional 
  849. portable text telephone that is permanently affixed within, or 
  850. adjacent to, the telephone enclosure.  In order to be usable with 
  851. a pay phone, a text telephone which is not a single integrated 
  852. text telephone pay phone unit will require a shelf large enough 
  853. (10 in (255mm) wide by 10 in (255 mm) deep with a 6 in (150 mm) 
  854. vertical clearance minimum) to accommodate the device, an 
  855. electrical outlet, and a power cord.  Movable or portable text 
  856. telephones may be used to provide equivalent facilitation.  A 
  857. text telephone should be readily available so that a person using 
  858. it may access the text telephone easily and conveniently.  As 
  859. currently designed pocket- type text telephones for personal use 
  860. do not accommodate a wide range of users.  Such devices would not 
  861. be considered substantially equivalent to conventional text 
  862. telephones.  However, in the future as technology develops this 
  863. could change.
  864.  
  865. A4.32 Fixed or Built-in Seating and Tables.
  866.  
  867. A4.32.4 Height of Tables or Counters.  Different types of work 
  868. require different table or counter heights for comfort and 
  869. optimal performance.  Light detailed work such as writing 
  870. requires a table or counter close to elbow height for a standing 
  871. person.  Heavy manual work such as rolling dough requires a 
  872. counter or table height about 10 in (255 mm) below elbow height 
  873. for a standing person.  This principle of high/low table or 
  874. counter heights also applies for seated persons; however, the 
  875. limiting condition for seated manual work is clearance under the 
  876. table or counter.
  877.  
  878. Table A1 shows convenient counter heights for seated persons.  
  879. The great variety of heights for comfort and optimal performance 
  880. indicates a need for alternatives or a compromise in height if 
  881. people who stand and people who sit will be using the same 
  882. counter area.
  883.  
  884. TABLE A1
  885. CONVENIENT HEIGHTS OF TABLES AND COUNTERS FOR SEATED PEOPLE1
  886. SHORT WOMEN
  887. TALL MEN
  888. CONDITIONS OF USE
  889. in
  890. mm
  891. in
  892. mm
  893. Seated in a wheelchair:
  894.     Manual work:
  895.     Desk or removable
  896. armrests
  897. 26
  898. 660
  899. 30
  900. 760
  901.     Fixed, full-size
  902. armrests2
  903. 323
  904. 815
  905. 323
  906. 815
  907.     Light, detailed work:
  908.     Desk or removable
  909. armrests
  910. 29
  911. 735
  912. 34
  913. 865
  914.     Fixed, full-size
  915. armrests2
  916. 323
  917. 815
  918. 34
  919. 865
  920.     Seated in a 16 in (405
  921. mm) high chair:
  922.     Manual work
  923. 26
  924. 660
  925. 27
  926. 685
  927.     Light, detailed work
  928. 28
  929. 710
  930. 31
  931. 7851All dimensions are based on a work-surface thickness of 1 1/2 
  932. in (38 mm) and a clearance of 1 1/2 in (38 mm) between legs and 
  933. the underside of a work surface.
  934.  
  935. 2This type of wheelchair arm does not interfere with the 
  936. positioning of a wheelchair under a work surface.
  937.  
  938. 3This dimension is limited by the height of the armrests:  a 
  939. lower height would be preferable.  Some people in this group 
  940. prefer lower work surfaces, which require positioning the 
  941. wheelchair back from the edge of the counter.
  942.  
  943. A4.33 Assembly Areas.
  944.  
  945. A4.33.2 Size of Wheelchair Locations.  Spaces large enough for 
  946. two wheelchairs allow people who are coming to a performance 
  947. together to sit together.
  948.  
  949. A4.33.3 Placement of Wheelchair Locations.  The location of 
  950. wheelchair areas can be planned so that a variety of positions 
  951. within the seating area are provided.  This will allow choice in 
  952. viewing and price categories.
  953.  
  954. Building/life safety codes set minimum distances between rows of 
  955. fixed seats with consideration of the number of seats in a row, 
  956. the exit aisle width and arrangement, and the location of exit 
  957. doors.  "Continental" seating, with a greater number of seats per 
  958. row and a commensurate increase in row spacing and exit doors, 
  959. facilitates emergency egress for all people and increases ease of 
  960. access to mid-row seats especially for people who walk with 
  961. difficulty.  Consideration of this positive attribute of 
  962. "continental" seating should be included along with all other 
  963. factors in the design of fixed seating areas.
  964.  
  965. A4.33.6 Placement of Listening Systems.  A distance of 50 ft (15 
  966. m) allows a person to distinguish performers' facial expressions.
  967.  
  968. A4.33.7 Types of Listening Systems.  An assistive listening 
  969. system appropriate for an assembly area for a group of persons or 
  970. where the specific individuals are not known in advance, such as 
  971. a playhouse, lecture hall or movie theater, may be different from 
  972. the system appropriate for a particular individual provided as an 
  973. auxiliary aid or as part of a reasonable accommodation.  The 
  974. appropriate device for an individual is the type that individual 
  975. can use, whereas the appropriate system for an assembly area will 
  976. necessarily be geared toward the "average" or aggregate needs of 
  977. various individuals.  A listening system that can be used from 
  978. any seat in a seating area is the most flexible way to meet this 
  979. specification.  Earphone jacks with variable volume controls can 
  980. benefit only people who have slight hearing loss and do not help 
  981. people who use hearing aids.  At the present time, magnetic 
  982. induction loops are the most feasible type of listening system 
  983. for people who use hearing aids equipped with "T-coils," but 
  984. people without hearing aids or those with hearing aids not 
  985. equipped with inductive pick-ups cannot use them without special 
  986. receivers.  Radio frequency systems can be extremely effective 
  987. and inexpensive.  People without hearing aids can use them, but 
  988. people with hearing aids need a special receiver to use them as 
  989. they are presently designed.  If hearing aids had a jack to allow 
  990. a by-pass of microphones, then radio frequency systems would be 
  991. suitable for people with and without hearing aids.  Some 
  992. listening systems may be subject to interference from other 
  993. equipment and feedback from hearing aids of people who are using 
  994. the systems.  Such interference can be controlled by careful 
  995. engineering design that anticipates feedback sources in the 
  996. surrounding area.
  997.  
  998. Table A2, reprinted from a National Institute of Disability and 
  999. Rehabilitation Research "Rehab Brief," shows some of the 
  1000. advantages and disadvantages of different types of assistive 
  1001. listening systems.  In addition, the Architectural and 
  1002. Transportation Barriers Compliance Board (Access Board) has 
  1003. published a pamphlet on Assistive Listening Systems which lists 
  1004. demonstration centers across the country where technical 
  1005. assistance can be obtained in selecting and installing 
  1006. appropriate systems.  The state of New York has also adopted a 
  1007. detailed technical specification which may be useful.
  1008.  
  1009. Table A2.  Summary of Assistive Listening Devices
  1010.  
  1011.     System
  1012.     Advantages
  1013.     Disadvantages
  1014.     Typical
  1015. Applications
  1016. Induction Loop
  1017.     Transmitter:
  1018.     Transducer
  1019.     wired to
  1020.     induction
  1021.     loop around
  1022.     listening
  1023.     area.
  1024.     Receiver:
  1025.     Self-
  1026.     contained
  1027.     induction
  1028.     receiver or
  1029.     personal
  1030.     hearing aid
  1031.     with
  1032.     telecoil.
  1033. Cost-Effective
  1034. Low
  1035. Maintenance
  1036. Easy to use
  1037. Unobtrusive
  1038.     May be
  1039.     possible to
  1040.     integrate
  1041.     into
  1042.     existing
  1043.     public
  1044.     address
  1045.     system.
  1046.     Some hearing
  1047.     aids can
  1048.     function as
  1049.     receivers.
  1050.     Signal spills
  1051.     over to
  1052.     adjacent
  1053.     rooms.
  1054. Susceptible to
  1055. electrical
  1056. interference.
  1057. Limited
  1058. portability
  1059. Inconsistent signal
  1060.     strength
  1061. Head position affects
  1062.     signal
  1063.     strength.
  1064.     Lack of
  1065.     standards
  1066.     for
  1067.     induction
  1068.     coil
  1069.     performance.
  1070.     Meeting areas
  1071.     Theaters
  1072.     Churches and
  1073. Temples
  1074.     Conference
  1075. rooms
  1076.     Classrooms
  1077.     TV viewing
  1078. FM
  1079.     Transmitter:
  1080.     Flashlight-
  1081.     sized worn
  1082.     by speaker.
  1083.     Receiver:
  1084.     With
  1085.     personal
  1086.     hearing aid
  1087.     via DAI or
  1088.     induction
  1089.     neck-loop
  1090.     and
  1091.     telecoil; or
  1092.     self-
  1093.     contained
  1094.     with
  1095.     earphone(s).
  1096. Highly
  1097.     portable
  1098.     Different
  1099.     channels
  1100.     allow use by
  1101.     different
  1102.     groups
  1103.     within the
  1104.     same room.
  1105. High user
  1106. mobility
  1107.     Variable for
  1108.     large range
  1109.     of hearing
  1110.     losses.
  1111. High cost of
  1112.     receivers
  1113. Equipment
  1114. fragile
  1115. Equipment
  1116. obtrusive
  1117. High
  1118. maintenance
  1119. Expensive to
  1120. maintain
  1121. Custom fitting to
  1122. individual user may be required.
  1123.     Classrooms
  1124.     Tour groups
  1125.     Meeting areas
  1126.     Outdoor
  1127. events
  1128.     One-on-one
  1129. Infrared
  1130.     Transmitter:
  1131.     Emitter in
  1132.     line-of-
  1133.     sight with
  1134.     receiver.
  1135.     Receiver:
  1136.     Self-
  1137.     contained.
  1138.     Or with
  1139.     personal
  1140.     hearing aid
  1141.     via DAI or
  1142.     induction
  1143.     neckloop and
  1144.     telecoil.
  1145. Easy to use
  1146.     Insures
  1147.     privacy or
  1148.     confidential
  1149.     ity
  1150. Moderate cost
  1151.     Can often be
  1152.     integrated
  1153.     into
  1154.     existing
  1155.     public
  1156.     address
  1157.     system.
  1158.     Line-of-sight
  1159.     required
  1160.     between
  1161.     emitter and
  1162.     receiver.
  1163. Ineffective
  1164. outdoors
  1165. Limited
  1166. portability
  1167. Requires
  1168. installation
  1169. Theaters
  1170. Churches and
  1171. Temples
  1172. Auditoriums
  1173. Meetings requiring confidential ity
  1174. TV viewing
  1175. Source:  Rehab Brief, National Institute on Disability and 
  1176. Rehabilitation Research, Washington, DC, Vol. XII, No. 10, 
  1177. (1990).
  1178.  
  1179. A5.0 Restaurants and Cafeterias.
  1180.  
  1181. A5.1 General.  Dining counters (where there is no service) are 
  1182. typically found in small carry-out restaurants, bakeries, or 
  1183. coffee shops and may only be a narrow eating surface attached to 
  1184. a wall.  This section requires that where such a dining counter 
  1185. is provided, a portion of the counter shall be at the required 
  1186. accessible height.
  1187.  
  1188. A7.0 Business and Mercantile.
  1189.  
  1190. A7.2(3) Assistive Listening Devices.  At all sales and service 
  1191. counters, teller windows, box offices, and information kiosks 
  1192. where a physical barrier separates service personnel and 
  1193. customers, it is recommended that at least one permanently 
  1194. installed assistive listening device complying with 4.33 be 
  1195. provided at each location or series.  Where assistive listening 
  1196. devices are installed, signage should be provided identifying 
  1197. those stations which are so equipped.
  1198.  
  1199. A7.3 Check-out Aisles.  Section 7.2 refers to counters without 
  1200. aisles; section 7.3 concerns check-out aisles.  A counter without 
  1201. an aisle (7.2) can be approached from more than one direction 
  1202. such as in a convenience store.  In order to use a check-out 
  1203. aisle (7.3), customers must enter a defined area (an aisle) at a 
  1204. particular point, pay for goods, and exit at a particular point.
  1205.